The temperature transmitter for Pt100 or Pt1000 sensors is ideal for simple retrofitting of plants. The user can choose between an analog output or an IO-Link interface. The cable transmitter's high level of vibration and shock resistance makes it reliable and durable.
general technical data | |
---|---|
Version | JUMO dTRANS T09 AS (analog output), JUMO dTRANS T09 DS (digital output) |
Format | Cable transmitter |
Mounting | In the cable line |
Measurement input | RTD temperature probe with Pt100 or Pt1000, four-wire connection |
Connection | M12 (on both sides) |
Output | Current DC 4 to 20 mA or IO-Link interface |
Housing | Stainless steel |
Protection type | IP66, IP67, and IP69 |
Approval | cULus |
Special features | Customer-specific configuration possible, high degree of vibration and shock resistance, separated from temperature sensor (thermally and mechanically decoupled) |